© Copyright 2026. All Rights Reserved
UT276A+Earth Ground Tester series can quickly and safely measure the grounding system without disconnecting circuit ground lines or the need of auxiliary electrodes. It can measure resistance from 0.01Ω with a resolution of 0.001Ω. UT275 can also measure leakage current up to 30A. These clamps’double insulation design makes them durable tools for outdoor work and effective in blocking interference from the environment.
| Specifications | Range | UT276A+ |
| Certifications | CE, RoHS (UT276A+/278A+ only) | |
| Category ratings | CAT III 300V | |
| Earth Ground Resistance (Ω) | 0.01~0.099Ω | ±(1%+0.01) |
| 0.1~0.99Ω | ±(1%+0.01) | |
| 1~49.9Ω | ±(1%+0.1) | |
| 50~99.5Ω | ±(1.5%+0.5) | |
| 100~199Ω | ±(2%+1) | |
| 200~395Ω | ±(5%+5) | |
| 400~590Ω | ±(10%+10) | |
| Display count | 4 digits LCD display | |
| Jaw opening | 32mm | |
| Visual and audible alarm | √ | |
| Auto power off | √ | |
| Jamming signal recognition | √ | |
| Over-range display | √ | |
| Data storage | 300 | |
| Display type | EBTN | |
| General Characterisitics of UT276A+Earth Ground Tester | ||
| Power | 1.5V battery (LR6) x 4 | |
| Display | 47mm x 28.5mm | |
| Product net weight | 1.18kg | |
| Product size | 285mm x 85mm x 56mm | |
| Standard accessories | Batteries, test ring, English manual | |
| Standard individual packing | Gift box, tool box | |
| Standard quantity per carton | 1pcs | |
| Standard carton measurement | 370mm x 110mm x 300mm | |
| Standard carton gross weight | 2.6kg | |